This document establishes the specifications for a two conductor plenum-rated shielded cable used for remote control and signaling power limited circuit applications.
Specifications
- • Number of Conductors: 2/C
- • Conductor: 18AWG Stranded Bare Copper
- • Insulation Material: Plenum Polymer Nominal
- • Color Code: Gray
- • Shield: Aluminum/Polyester Tape (100% Coverage)
- • Drain: Solid Tinned Copper
- • Jacket Material: Plenum Polymer
- • Nominal Jacket Thickness: 0.015 in.
- • Nominal Diameter: 0.154 in.
- • Surface Print: Sequential Footage Marking
Electricals
• Suggested Working Voltage: 300 Volts, rms.
• Nom. Capacitance Cond-Cond: 41 pF/FT
• Nom. Impedance: 53 Ohms
• Nom. Velocity pf Propagation: 55%
• Nom. DCR: 6.92 Ohms/1M’
Temperature Rating
• Operation: -20°C to +60°C
• Nominal Weight: 22 lbs. / 1,000 feet
Standards
• National Electric Code – Article 800, 760
• UL Subject 444, Type CMR FT4
• UL Subject 1424, Type FPLR
Codes & Listings
• C(ETL)US CMR